DL/T 645-2007

Purpose​

This plugin reads multifunction-meter data by DL/T 645-2007 data identifier and performs controlled close-permit or trip operations after password and operator-code configuration.

Open the plugin and supported scope​

Create a TCP client, TCP server, serial, or UDP channel, then create a device using DL/T 645-2007. Supported types include Boolean, Byte, common integers, Float, Double, String, and Decimal.

Plugin properties​

DL/T 645-2007 also inherits common read/write timeout, retry, write-priority, serial/TCP, and DTU settings; see Collection Configuration.

SettingDefaultDescription
Default address11111111111112-digit meter communication address used when a variable does not override it.
Operator code-Four-byte hexadecimal operator code required by control operations.
Password-Four-byte hexadecimal password. Trip/close supports only level-02 plaintext passwords. Keep it out of screenshots and logs.
PreambleFEFEFEFEWake-up prefix sent before the frame.
Control validity5 minutesRange 1 to 60; used to create the trip/close deadline.
DTU ID-Used for a DTU service connection.

Data-identifier addresses​

Enter an eight-digit data identifier from the meter point list. Use S=123456789012 to override the meter address for one variable, and R=false to disable data-byte reversal (the default is R=true), for example S=123456789012;02010100;R=false. One address may contain only one data identifier, station override, and reversal option.

AddressCommon meaning
02010100Phase-A voltage
02020100Phase-A current
02030000Instantaneous total active power
00000000Current combined active total energy
00010000Current forward active total energy

Special methods​

MethodPurposeConfiguration
ClosePermitAsyncPermit closingSelect the method, set address to [], set protection to write-only; any write triggers it.
TripAsyncTripSelect the method, set address to [], set protection to write-only; any write triggers it.

Trip and close change the power state. Verify meter address, password, operator code, validity, user permission, and site safety first.

Functions​

FunctionPurpose
Read and writeRead a confirmed point and write only to an approved test point.
MessagesView sent and received frames, protocol fields, and error details.

Device debug​

Open Development Configuration → Collection Configuration, select the DL/T 645-2007 device and click More Functions, then open Debug.

FeaturePurpose
Read/WriteReads one or multiple data identifiers. Writes are only for approved test data.
MessagesShows 645 requests, responses, and checksum results.

DL/T 645-2007 read and write

The common Overview screenshot is not repeated. Execute trip/close through the configured special-method variable, not a normal data identifier.

Verify the configuration​

  1. Read one known data identifier and compare it with the meter display.
  2. Check meter address, control code, and checksum under Messages.
  3. Perform trip/close only in an approved site test and verify physical feedback.

Troubleshooting​

SymptomCheck
Meter does not respondChannel, baud rate, default address, preamble, and network/serial link.
Data identifier failsIdentifier, meter support, data type, and permission.
Value is incorrectIdentifier, scaling, decimal places, and data type.
Trip/close failsLevel-02 password, operator code, validity, meter address, control permission, and device state.